What are the technical requirements for Siemens 8DJH switchgear?

Feb 23rd,2024 425 Views
General requirements for Siemens 8DJH switchgear

1.Three-poleprimary enclosure, metal-enclosed
2.Weldedswitchgear vessel without seals, made of stain-   less steel, with welded-in bushings for electrical connec- tions and mechanical components

3.Insulatinggas SF6  (fluorinated greenhouse gas)
4.Maintenance-free componentsunder normal ambient conditions according to IEC 62271-1 and VDE 0671-1
5.Three-position switch-disconnector withload-break function and make-proof earthing function
6.Vacuumcircuit-breaker
7.Cable connection with outside-coneplug-in system

– In ring-main and circuit-breaker feeders with bolted contact (M16)

– In transformer feeders with plug-in contact or optionally with bolted contact (M16)

  • Wall-standing or free-standing arrangement
  • Pressurerelief downwards, optionally to the rear or upwards via pressure absorber systems.

Interlocks

  • According toIEC 62271-200 and VDE 0671-200
  • Logicalmechanical interlocks prevent maloperation
  • Logicalmechanical interlocks and the constructive

features of the three-position switches prevent mal-   operation as well as access to the cable connection of the feeders and HV HRC fuses under voltage

  • Impermissibleand undesired operations can be prevent-  ed by means of locking devices provided at the switching devices
  • A detailed description of allinterlocking options is available on page 51.

Insulating system

  • Switchgearvessel filled with SF6 gas
  •  Features ofSF6  gas:

– Non-toxic

– Odorless and colorless

– Non-inflammable

– Chemically neutral

– Heavier than air

– Electronegative (high-quality insulator)

– Global Warming Potential GWP = 22,800

  • Pressure of SF6gas in the switchgear vessel (absolute values at 20 °C):

– Rated filling level: 150 kPa

– Design pressure: 180 kPa

– Design temperature of the SF6 gas: 80 °C

– Operating pressure of bursting disc: ≥ 300 kPa

– Bursting pressure: ≥ 550 kPa

– Gas leakage rate: < 0.1 % per year.