First, power supply
1, first check whether the live display is energized, and whether the SF6 barometer is above the minimum safety value.
2. Ground switch opening: Insert the operation handle into the ground switch operating hole, turn counterclockwise to open the gate, then the center of the panel is in shape, the lower door panel is locked.
3, load switch closing: insert the operation handle into the load switch operating hole, turn clockwise to close, this time the sign is in shape. The live display shines.
2. Power failure
1, first check whether the live display is energized, and whether the SF6 barometer is above the minimum safety value.
2. Load switch opening: Insert the operating handle into the operating hole of the load switch, turn counterclockwise to open the gate, at this time, the closing indicator should be put out in the shape of the live display.
note
1. If the power supply enters from the upper end of the switch, the live display will be extinguished and shiny with the switch closing.
2, if the power supply enters from the lower end of the switch, the live display has been shining. This power supply is constant, do not close the ground switch.
3. When the relative pressure value of the barometer is less than 0.035MPa, do not send power, please contact the company of the cabinet.