Case Details
Common features
All modules share many common features. These are described in the chapter “SafeRing/SafePlus configurations”.
Standard features
- 630 A vacuum circuit-breaker forfeederprotection
- Mechanism with operatingsequence;O – 0.3 s
– CO – 3 min – CO
- Auto-reclosing capability
- Vacuum circuit-breaker with downstream
three-position disconnector/earthing switch
- Three-position single springmechanism fordisconnector/earthing switch
- Interlockingbetweenvacuum circuit-breaker and disconnector/earthing switch
- Switchposition indication for vacuum circuit-breaker and disconnector/earthing switch
- Mechanical counter
- Cablebushingshorizontally in front Interface C (400 series bolted) with integrated capacitor for
- voltage indication
- Cablecompartmentcover allowing surge arrestor or double cable connection
-
Optional features as factory mounted
Interface C (400 series bolted) combisensors
with integrated voltage divider for voltage
indication and integrated sensor for current
and voltage monitoring
- Arcproof cable cover(IAC AFL 16/20 kA 1 sec.)
- Arc suppressor with signal(1NO) wired toterminals
Optional features also available as retrofit
- Motor operation forvacuumcircuit-breaker
- Auxiliary switches: Vacuum circuitbreaker
position 2NO+2NC, disconnector position
2NO+2NC, earthing switch position 2NO+2NC
- Undervoltagerelease with/without time delay
- Blockingmagnet toprevent unintended operation
- Advancedrelays typeREF, REX and others
Interlocking
Rules are same as for standard V-module, except for lockable push buttons.